Trung tâm báo cháy Protect

Trung tâm báo cháy Protect

Trung tâm báo cháy Protect

Chi tiết sản phẩm:

Temperature Range0 – 40°C.
Maximum Humidity85% Non-Condensing.
Working Voltage21.5 – 30V dc.
Secure NetworkDual channel RS485 fault tolerant communications network for up to 100 nodes.
3 wire loop (2 Data & 0V), maximum 1km between nodes.
Node Power SupplyFault monitored dual path 24V dc from 6400/BC range PSU 4 wire plus 2 wire (2 Primary Power, 2 signals) (2 Sec. Power).
Total Node LoadMaximum load to a 6400/LPN or 6400/DCN/LPN is 6A.

6400/DCN

Standby Load
(Mains Fail Condition)
210mA.
Alarm Load
(Mains Fail Condition)
390mA.
DisplayQuarter VGA Backlit Graphics LCD
Zones100 Zone Fire indicators, plus common ‘FIRE’ indicator. Expandable to 800
Printer40 column low noise thermal printer
NodesThe 6400/DCN counts as one node on the network
RS232 PortsTwo full duplex RS232 ports for site programming, BMS, Colour Graphics or pager system interfacing
Auxiliary Output SupplyTwo sets of 24V dc output terminals. Total load 1A
Common Fire Output
(fire station)
24V dc fully monitored output rated at 20mA. 1K EOL
Common Fault Output
(fire station)
24V dc fully monitored output rated at 20mA. 1K EOL.
Dimensions (mm)440(W) x 385(H) x 104(D)
ApprovalsLPCB Certificate No: 201ad/01
EC Certificate No: 0832-CPD-1434
Relevant Standard: EN 54-2

6400/LPN

Standby Load
(Mains Fail Condition)
250mA (2 loop) 310mA (4 loop)
Alarm Load
(Mains Fail Condition)
480mA (2 loop) 540mA (4 loop)
Analogue Addressable Loops2 to 4 loops, each with 127 address capacity per loop. Total 6400/LPN capacity 4 loops, 508 addresses.
Total Loop Load600mA per loop including all loop connected devices.
NodesThe 6400/LPN counts as one node on the network.
Programmable Alarm Outputs8 monitored 24V dc sounder circuits 1A rated. 47K EOL. 6 non monitored – clean changeover contacts (1A rated @24V).
Expansion modules available to increase alarm output capability. Up to 127 programmable alarm outputs per loop using loop output devices. Total node load 6A.
Auxiliary Output SupplyFour sets of 24V dc output terminals. Total load 1A.
Common Fire Output
(fire station)
24V dc fully monitored output rated at 20mA. 1K EOL. Dedicated Clean Changeover contacts (1A rated @24V)
Common Fault Output
(fire station)
24V dc fully monitored output rated at 20mA. 1K EOL. Dedicated Clean Changeover contacts (1A rated @24V)
Software Input SwitchesClass change, bomb alert. Plus four additional non-dedicated inputs for day/night mode, etc
Dimensions (mm)440(W) x 385(H) x 144(D).
Approvals(2 loop)
LPCB Certificate No: 201ad/02
EC Certificate No: 0832-CPD-1435
Relevant Standard: EN 54-2 & 4.(4 loop)
LPCB Certificate No: 201ad/03EC Certificate No: 0832-CPD-1436Relevant Standard: EN 54-2 & 4.

6400/DCN/LPN

OverviewCombined 6400/DCN and 6400/LPN nodes within a common enclosure. The full specification for a 6400/LPN applies plus DCN controls.
Standby load
(Mains Fail Condition)
380mA (2 loop) 440mA (4 loop).
Alarm Load
(Mains Fail Condition)
770mA (2 loop) 830mA (4 loop).
Nodes  The 6400/DCN/LPN counts as TWO nodes on the network.
Dimensions (mm)440(W) x 385(H) x 144(D).
Approvals(2 loop)
LPCB Certificate No: 201ad/04
EC Certificate No: 0832-CPD-1437
Relevant Standard: EN 54-2 & 4

(4 loop) LPCB Certificate No: 201ad/05
EC Certificate No: 0832-CPD-1438
Relevant Standard: EN 54-2 & 4.

Chia sẻ: